Data errors
Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
68
Control parameter Control parameter error
Status classification
[Maintenance required]
Recommended action
Confirm error, perform reset and re-initialize the positioner.
69
Poti parameter Parameter error of the digital potentiometer.
Status classification
[Maintenance required]
Recommended action
Confirm error, perform reset and re-initialize the positioner.
70
Calibration parameter Error in the production calibration data. Subsequently, the device
runs on default values.
Status classification
[Maintenance required]
Recommended action
Return the positioner to SAMSON AG for repair.
71
General parameters Parameter errors that are not critical for the control.
Status classification
[Maintenance required]
Recommended action
Confirm error.
Check and, if necessary, reset required parameters.
73
Internal device error 1 Internal device error
Status classification
[Maintenance required]
Recommended action
Return the positioner to SAMSON AG for repair.
74
PA parameters Parameter errors that are not critical for the control.
Status classification
[Maintenance required]
Recommended action
Confirm error and perform reset.
EB 8384-4 EN 93
Code list