EB 8384-4 EN 121
Addendum Page 11
Revisions Control No. 1: March.2006 Addendum to EB 8384-5 EN
FM approved for hazardous locations:
Ex nA II T6; Ex nL IIC T6 Zone 2.
Class I, II, Div. 2 Groups A, B, C, D, E+F. Field enclosure NEMA 4X
Model 3730-43/3730-53
Positioners
11+
Limit switch circuit 2
81+ Forced venting function
Terminal No.
FM-approved
termination with
R = 90 . . .100Ω,
C = 0 . . .2,2µF
FM-approved
apparatus suitable
for FIELDBUS
FM-approved
apparatus suitable
for FIELDBUS
FM-approved associated
apparatus suitable
for Profibus PA or FOUNDATION FF
FIELDBUS
Binary contact 2
Isolating amplifier 1 or 2
Hazardous
Location
Safe
Location
87+ Binary contact 1
88- circuit 4
External position sensor
(optionally)
Serial interface,
FM-approved
UNSPECIFIED APPARATUS
e.g. transmitter relay
The installation must be in accordance with the National Electrical
Code ANSI/NFPA 70 and ANSI/ISA RP 12.06.01
Addendum Page 12
Revisions Control No. 1: March.2006 Addendum to EB 8384-5 EN
Installation drawing Control Relay KHA5-OTI/Ex2, KHA6-OTI/Ex1 or
KHA6-OTI/Ex2 with Model SJ-b-N Proximity Sensor
System parameters
Control Relay
Terminal No.
Groups
L
[ mH ]
C
[ µF ]
V
0C
[ V ]
I
SC
[ mA ]
V
max
[ V ]
R
min
[ Ω ]
A + B 192 2,66
C + E 671 7,9
1-3; 2-3
4-6; 5-6
D, F, G 1000 21,3
10,5 13
10,5 811
HAZARDOUS
SAFE
LOCATION
Ex nA II T6; Ex nL IIC T6 Zone 2.
Class I, II, Div. 2 Groups A, B, C, D, E+F.
to intrinsically
safe output
Model 3730-43
or 3730-53
+
42-
External position sensor
(optionally)
terminal No.
Proximity sensor
software limit switch
intrinsically output
to sensor or contact
channel 2
intrinsically output
to sensor or contact
channel 1
to one common
line possible
1+ 12+
2+ 11+
3- 10-
Switch-Isolators
Type KHA5 – OTI/Ex2
or KHA6 - OTI/Ex1
4+ 9+
5+ 8+
6- 7-
87+
88-
Model designation code Type KHab – cExde
a= Supply Voltage type A or D
a=AC, d=DC
b= Supply Level
2=24V DC±15%; 5=120V AC +10%-15%;
6=230V AC+10%-15%;
c= Output type RTA/; RW1/; SS1/; SS2/; RS1/;
SR/; ST-or SOT
d= Number of channels 1 or 2
e= Power rail designation, P, 2S.P or GS.P
(includes Model KHD2-EB-PB Power Feed
Module) or Blank
Each pair of I.S. wires must be protected by a shield that is grounded at the I.S. Ground. The shield must be extend as close
to the terminals as possible installation shall be in accordance with the National
Electrical Code ANSI/NFPA 70 and ANSI/ISA RP 12.06.01.
The total series inductance and shunt capacitance of shield wiring shall be restricted to the following maximum values
maximum capacitance of each inductive sensor 30nF
maximum inductance of each inductive sensor 100µH