Error appendix
Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
65
Hardware Initialization key jammed
A hardware error has occurred, the positioner changes to the
fail-safe position (
SAFE).
Status classification
Maintenance alarm (cannot be classified)
Recommended action
Confirm error and return to the automatic operating mode, or
perform a reset and re-initialize the device. If this is not success
-
ful, return device to SAMSON AG for repair.
66
Data memory The writing of data to the data memory does not work anymore,
e.g. when the written data deviate from the read data.
Valve moves to the fail-safe position.
Status classification
Maintenance alarm (cannot be classified)
Recommended action
Return the positioner to SAMSON AG for repair.
67
Test calculation The hardware controller is monitored by means of a test
calculation.
Status classification
Maintenance alarm (cannot be classified)
Recommended action
Confirm error. If this is not possible, return the positioner to
SAMSON AG for repair.
92 EB 8384-4 EN
Code list