Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Default No
Turn
→
Code 3, display: No
Press , Code 3 blinks
Turn
→
YES
Press , display
Enter the pin position and nominal range:
Pin position
Default
No
Nominal range
(locked with Code 4 = No)
Turn
→
Code 4
Press , Code 4 blinks
Turn
→
Pin position on lever (see rele
-
vant section on attachment)
Press .
Turn
→
Code
5
Press , Code 5 blinks
Turn
→
Nominal travel/angle
Press .
Select the initialization mode:
Initialization mode
Default
MAX
Turn
→
Code 6
Press , Code 6 blinks
Turn
→
NOM
Press to confirm the NOM as the initial
-
ization mode.
Start initialization:
4
Press INIT key to start initialization!
Note: After initialization, check the direction
of action and, if necessary, change it
(Code 7).
7.6.3 MAN – Initialization based
on a manually selected
range
Before starting initialization, move the con
-
trol valve manually to the OPEN position by
turning in small steps. The valve must
move to the required valve position with a
monotonically increasing signal pressure.
The positioner calculates the differential
travel/angle using the OPEN and CLOSED
positions and adopts it as the operating
range with limits of travel/angle range start
EB 8384-4 EN 63
Start-up – Settings