(Code 8) and travel/angle range end
(Code 9).
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Default No
Turn
Code 3, display: No
Press , Code 3 blinks
Turn
YES
Press , display
Enter the pin position:
Pin position
Default
No
Turn
Code 4
Press , Code 4 blinks
Turn
Pin position on lever (see rele
-
vant section on attachment)
Press . The reading of the nominal range
appears in mm/°.
Select the initialization mode:
Initialization mode
Default
MAX
Turn
Code 6
Press , Code 6 blinks
Turn
MAN
Press to confirm the MAN as the initial
-
ization mode.
Enter OPEN position:
Manual set point
(the current angle of rota-
tion is displayed)
Turn
Code 0
Press , Code 0 blinks
Turn
MAN
Press
Turn
Code
1
Press , Code 1 blinks
Turn until the valve reaches its OPEN po
-
sition.
Press to confirm the OPEN position.
Start initialization:
4
Press INIT key to start initialization!
64 EB 8384-4 EN